Direct-to-chip (DTC) liquid cooling removes roughly 70–75% of the heat from a high-power rack — but the remaining 25–30% still has to leave the building as airflow. That single fact, documented in Vertiv’s liquid cooling white paper, is why cable-entry sealing and airflow management remain relevant in AI data centers even as cold plates and coolant distribution units (CDUs) take over the heaviest thermal loads.
If you operate or retrofit a facility combining liquid-cooled GPU racks with conventional air-cooled equipment, this article walks through where cable-entry openings still matter, what changes during a liquid-cooling retrofit, and how to specify brush seals for those applications.
Why airflow still matters with direct-to-chip cooling
In a DTC system, cold plates transfer heat from CPUs and GPUs into circulating coolant, which a CDU delivers to the facility’s cooling infrastructure. But not every component is liquid-cooled. Depending on server architecture, memory, power supplies, storage drives, and networking gear may still depend on air — and some facilities run liquid-cooled AI clusters alongside fully air-cooled racks. Vertiv’s liquid cooling overview describes this hybrid arrangement as the typical condition in direct-to-chip deployments.
The practical question for operators and retrofit contractors is therefore not “does this facility use liquid cooling?” but “which equipment still depends on controlled airflow, and which openings connect air zones that shouldn’t mix?”
Four cable-entry openings to review during a retrofit
Introducing liquid cooling changes rack layouts, coolant piping routes, and cable density. Four categories of openings typically remain on the airflow-management checklist.
Rack-mounted cable pass-throughs
Power and network cables frequently pass between rack compartments or through dedicated mounting panels. Where an opening connects the front and rear airflow zones of a cabinet, unused space around cable bundles becomes a bypass path.
Rack brush panels cover that unused space while letting cables pass through. Custom 1U, 2U, and non-standard panels can be designed around the actual opening dimensions, cable layout, and mounting pattern — which matters in AI racks where cable density rarely matches a standard cutout.
Cabinet roof, base, and side cutouts
Not every cable entry sits in a standard rack unit. Server cabinets, network enclosures, and supporting equipment may have cutouts in roof, base, or side panels — and equipment upgrades often leave those cutouts larger than the replacement cable bundles require.
For long or irregularly sized linear openings, metal-channel strip brushes offer a drawing-based solution: a formed metal backing provides a defined mounting section, while nylon filaments form a flexible contact edge. Dimensions, holder profile, and filament position are selected against the installed structure, not a catalog size.
Raised-floor cable cutouts
Where a raised-floor plenum distributes cooling air, unsealed cable cutouts let conditioned air escape before it reaches equipment intakes. This is not optional housekeeping in colocation environments: Equinix’s Customer Installation Guidelines require brush seals or rubber grommets on all cable entries from the raised floor into cabinets, and the US ENERGY STAR program lists floor grommets among practical measures for improving cooling airflow efficiency.
Purpose-designed brush grommets — such as Chatsworth Products’ Raised Floor Grommet — accommodate dense cable bundles while minimizing the open area around them. For in-service installations, split or accessible configurations allow installation without disconnecting live cables.
Note that not every AI facility uses raised-floor air distribution — assess sealing needs against the actual cooling design, not against a generic checklist.
Containment panel cable-tray openings
Hot-aisle and cold-aisle containment systems separate supply and exhaust airflow. Where cable trays pass through containment panels, surrounding openings interrupt that separation. Custom brush strips can suit non-rated linear openings, particularly where cables need continued access during maintenance — provided the brush matches the opening geometry and the containment system’s operating requirements.
Keep cable seals separate from pipe and fire penetrations
Liquid-cooling upgrades introduce coolant piping, CDU connections, and rack rearrangements — which creates an important distinction between two kinds of penetration:
- Cable-entry openings benefit from brush panels, strip brushes, and floor grommets: components designed to cover unused space while preserving cable access.
- Coolant-pipe and hose penetrations follow the cooling-system manufacturer’s specifications and the facility’s mechanical and safety design. A conventional brush strip is not a liquid-tight seal, a leak-containment device, or a substitute for an engineered pipe penetration. Fire-rated walls and floors likewise require tested firestop systems.
Keeping these functions separate prevents contractors from specifying an airflow accessory for a job it was never designed to do.
What to specify for an in-service installation
In an operating data center, installability and future maintenance access matter as much as initial fit. Before specifying a brush assembly, review:
- Opening geometry — location, dimensions, mounting surface, and its position relative to the intended airflow boundary
- Existing connections — bundle size, connector clearance, bend radius, and whether cables can be disconnected
- Brush construction — panel vs. metal-channel format, holder profile, filament material, trim height, fill density
- Maintenance access — whether the assembly can be opened or replaced without disturbing installed cables
- Project requirements — material documentation, fire-safety constraints, environmental conditions, required testing
For non-standard openings, an installation drawing or a sample of the existing mounting profile is the fastest way to reach the correct construction. Brushcustom’s cable-entry selection guide compares brush panels, blanking panels, and other closure methods in detail.
Measure the airflow result after installation
Covering an opening does not guarantee a measurable cooling improvement. The outcome depends on whether the opening crosses a meaningful airflow boundary, the pressure difference across it, and how much equipment still relies on air cooling. Facility teams should measure equipment inlet temperatures, airflow paths, and pressure conditions before and after installation — and account for changes in IT load and cooling controls. Brush seals are one component of an airflow-management strategy, not a standalone fix.
Cable-entry sealing for hybrid AI facilities
Liquid cooling changes how high-density AI servers reject heat, but it does not remove every cable-entry requirement. In hybrid liquid-and-air facilities, correctly selected brush panels, metal-backed strip brushes, and floor-opening assemblies close unnecessary gaps while preserving cable access. For retrofits, the priority is to identify the opening, understand its function, and match the component to the installed structure.